Truly the next generation of industrial UPS systems and commercial UPS systems, the Toshiba 4400 Series is a double-conversion, all insulated-gate bipolar transistor uninterruptible power system that features a digitally-controlled IGBT input rectifier, intelligent low harmonic pulse-width modulation of the output, and state-of-the-art electronic battery isolation circuitry.

Total front-access design requires zero rear-clearance and includes convenient features such as top, bottom, and/or side cable entry, standard sized air filter provisions, and lockable keyed doors. Small footprint and intuitive local touchscreen interface make it versatile and user-friendly, and it can be customized to your specific needs with such options as internal battery backup, internal transformers for specific voltage applications, and remote monitoring with the Toshiba RemotEye® 4 multi-protocol UPS.


Features & Benefits

  • Double-conversion, all insulated-gate bipolar transistor uninterruptible power system
  • Digitally-controlled IGBT input rectifier
  • Intelligent low harmonic pulse-width modulation of the output
  • State-of-the-art electronic battery isolation circuitry
  • Total front-access design requires zero rear-clearance
  • Top, bottom, and/or side cable entry, standard sized air filter provisions, and lockable keyed doors
  • Small footprint for ease of installation
  • Intuitive local touchscreen interface make it versatile and user-friendly
  • Can be customized with internal battery backup, internal transformers for specific voltage applications, and remote monitoring with the Toshiba RemotEye® 4 multi-protocol UPS.

Request a quote

 

Technical Specs

MODEL Model Number 4400X3X150XA 4400X3X200XA 4400X3X250XA 4400X3X300XA 4400X3X500XA 4400X3X800XA
Capacity 15 kVA (13.5 kW) 20 kVA (18 kW) 25 kVA (22.5 kW) 30 kVA (27 kW) 50 kVA (45 kW) 80 kVA (72 kW)
Topology True On-Line, Double-Conversion, All-IGBT Technology
INPUT Voltage (Standard) 208/120V Three-phase, Four-Wire + Ground Input*
Voltage Range -15% to +10% (Without Using Battery)
Power Factor > 0.98
Current THD < 5% at 100% Load
Frequency 50 ±5 Hz; 60 ±5 Hz
OUTPUT Voltage (Standard) 208/120 V: Three-Phase, Four-Wire + Ground**
Frequency 50/60 Hz, ±0.1% Auto-Sensing Standard. (50/60Hz Selectable, for
use as Frequency Converter)
Voltage Regulation ±2.0%
Power Factor 0.9 Lagging
Overload Inverter: 125% for 90 Seconds, 150% for 30 Seconds
Bypass: 125% for 10 Minutes, 1000% for 10
Milliseconds
BATTERY DC Link 288 VDC
Ripple Voltage < 0.5% DC
ENVIRONMENT Temperature Range 32° to 104°F (0° to 40°C)
Relative Humidity 5% to 95% Non-Condensing
Heat Rejection 4556
BTUs/Hour
6074
BTUs/Hour
7395
BTUs/Hour
9111
BTUs/Hour
15,186
BTUs/Hour
24,297
BTUs/Hour
Full-Load Efficiency 91.0%
25% Load Efficiency 88.8%
Altitude 3300 ft. (1000 m) Maximum Without Derating
Air Filtration Airflow Front to Top with Provisions for Front-Located Air
Filters
DIMENSIONS Dimensions 20.12″ (W) x 37.4″ (D) x
65.06″ (H) (511mm x 950mm x 1653mm)
32.1″ (W) x 31.8″ (D) x 73.6″ (H) (816mm x
807mm x 1870mm)
Weight*** 720 lbs. (326 kg) 1350 lbs. (612 kg) 1500 lbs. (680 kg)
COLOR O’Brien Black (Textured Powder Coat)
MONITORING Touchscreen Operator Interface, UPS Status N/O Dry Contacts,
RS232C Interface (Optional RemotEye® 4 Intelligent
Monitoring System)
OPTIONS Internal Batteries, Transformers, Dual-Input Feed, RemotEye® Intelligent Monitoring System, Remote Status Alarm Panel, Air
Filters
STANDARDS UL 1778, CUL, ISO9001, ISO14001:2004, ANSI C62.41 (IEEE 587),
NEMA/PET-1993, CE, IBC, & CBC (OSHPD)
WARRANTY 3-Year On-Site Warranty; 5-Year Warranty Available; See Toshiba
Warranty Policy for Full Details
SERVICE 24-Hour, 365-Day Technical Support: 1-877-867-8773
* Isolation and Auto Transformer
Options for Input Voltage Conversion
** Auto Transformer
Options for Output Voltage Conversion
*** Unit Weight Not
Including Internal Battery and Transformers
Specifications subject to change without
notice.

 

Industries & Applications

  • Critical network switching & processing equipment
  • Large-scale PLC controls
  • Medium-to-larger data centers
  • Hospital applications such as MRI, CT, or PET scanning equipment
  • Financial Institutions
  • Industrial applications
  • Pharmacological manufacturing

Request a quote

 

We respect your privacy and will never share your email address with anyone without your explicit permission.

Designed specifically as an industrial UPS system for the specific needs of the IT industry, the 4300 Series boasts one of the largest input voltage/frequency windows in the industry, which extends useful battery life. Features include true online double-conversion, an input power factor better than 98 percent, and input current THD less than 3 percent.

Frontend IGBT design allows the 4200FA to work optimally from zero to 100 percent load with less than 3 percent THD on the input, allowing for generator single-sizing. Optional matching battery cabinet and maintenance bypass cabinet allow for sixty combinations of three-phase/three-wire and three-phase/four-wire input/output voltages. Comes with a standard three year warranty.


Features & Benefits

  • True online double-conversion
  • “Line up and match” ancillary equipment [transformer, battery, and MBS cabinets]
  • Zero rear-clearance required
  • Complete front-access design with top, front, and side entry
  • Local touch-screen interface
  • 90 percent output power factor
  • Input Power Factor > 98 percent
  • Input Current < 3 percent

Request a quote

 

Technical Specs

4300 Series
Model Model Number 4310F3F300XAXX 4310F3F500XAXX
Capacity 30 KVA/27 KW 50 KVA/ 45 KW
Topology True On-Line, Double Conversion, & All IGBT Technology
INPUT Voltage 208/120 V: Three-Phase, Four-Wire + Ground/Bypass Input; 208/120 V: Three-Phase, Four-Wire + Ground
Voltage Range 208 V, -20% to +15% (166 to 239 V Without Using Battery)
Power Factor > 0.99
Current THD < 3% at 100% Load
Frequency 50 ±5 Hz; 60 ±5 Hz
OUTPUT Voltage 208/120 V: Three-Phase, Four-Wire + Ground
Frequency 50/60 Hz, ±0.1% (Can be Used as Frequency Converter)
Voltage Regulation ±1.0% (0.5% Typical)
Power Factor 0.9 Lagging
Overload Inverter: 125% for 90 Seconds, 150% for 30 Seconds Bypass: 125% for 10 Minutes, 1000% for 10 Milliseconds
BATTERY DC Link 288 VDC
Ripple Voltage < 0.5% DC
ENVIRONMENT Temperature Range 32° to 104°F (0° to 40°C)
Relative Humidity 5% to 95% Non-Condensing
Heat Rejection 8153 BTUs/Hour 15,019 BTUs/Hour
Full-Load Efficiency 91.90% 91.10%
25% Load Efficiency 88.00% 88.80%
Altitude 6600 ft. (2000 m) Maximum Without Derating
Audible Noise < 65 dBA at 1m Air Filtration; Standard Front Air Filter
DIMENSIONS Dimensions 22.1 x 31.6 x 73.6 in. (73.7 in. (H) with Fan Cage)
Weight 788 lbs. 867 lbs.
COLOR O’Brien Black (Textured Powder Coat)
COMMUNICATION OPTIONS RemotEye® III & Ethernet/SNMP
OPTIONS Dual-Input Feed
STANDARDS UL 1778, ULC, CE, FCC Class A, ISO9001, ISO14001, ANSI C62.41 (IEEE 587), & NEMA PE 1-1993
WARRANTY Three-Years On-Site Warranty; Five-Years Available; See Toshiba Warranty Policy for Full Details
SERVICE 24-Hour, 365-Day Technical Support: 1-877-867-8773

 

Industries & Applications

  • Critical network switching & processing equipment
  • Large-scale PLC controls
  • Medium-to-larger data centers
  • Financial Institutions
  • Industrial applications

Request a quote

 

We respect your privacy and will never share your email address with anyone without your explicit permission.

Noted for its versatility, and offering the largest input voltage/frequency window in the industry, the 4200FA Series is designed to be a high-performance state-of-the-art commercial or industrial UPS system suitable for use across a wide breadth of industrial UPS system applications.

Features include true online double-conversion, an input power factor better than 98 percent, and input current THD less than 3 percent. Frontend IGBT design allows the 4200FA to work optimally from zero to 100 percent load with less than 3 percent THD on the input, allowing for generator single-sizing. Proprietary technology lengthens battery life. The CT models feature internal batteries and maintenance bypass— without the need for additional cabinets. Comes with a standard three year warranty.


Features & Benefits

  • Largest input voltage/frequency window in the industry
  • Suitable for use across a wide breadth of industries and applications
  • True online double-conversion
  • Input power factor better than 98 percent
  • Input current THD less than 3 percent
  • Frontend IGBT design works optimally from zero to 100 percent load with less than 3 percent THD on the input—allowing for generator single-sizing
  • Proprietary technology lengthens battery life
  • Three year warranty

Request a quote

 

Technical Specs

4200FA CT Standard Specifications
Model Number
T42F3F150XAMBN
T42F3F250XAMBN
T42F3F300XAMBN
T42F3F500XAMBN
Capacity kVA/kW
15/12
25/20
30/24
50/40
Topology
True On-line, Double Conversion, IGBT Pwm, with Active
Input Power Factor Correction
Input Voltage
208/120 V, 3 Phase, 4 w + Gnd
Voltage Range
+10% to -30%; +20% to -30% online (without utilizing
battery)
Power Factor
Greater than 0.99
Current THD
Less than 3%
Frequency
50/60 Hz (Range 45 to 65 Hz)
Current Limit
115% Maximum
Output Voltage
208/120 V, 3-Phase, 4 w + Gnd
Frequency
50/60 Hz � 0.01% (Can be Used as a Frequency Converter)
Voltage Regulation
< 1% Balanced, 100% Load Step / < 2% Unbalanced,
100% Load Step
Overload (Inverter)
125% for 90 Seconds, 150% for 30 Seconds
Overload (Bypass)
125% for 10 Minutes, 1000% for 10 milliseconds
Battery Time (Full / Half Load)
9/26 Minutes
4/13 Minutes
3/10 Minutes
4.5/14 Minutes
DC Link
288 VDC
Ripple Voltage
< 0.5% DC
Environment Temperature Range
0 to 40� C (Operating) / -20 to +50� C (Storage)
Relative Humidity
0 to 95% Non-Condensing
Heat Rejection
8,988 BTUs
12,043 BTUs
14,451 BTUs
18,611 BTUs
Efficiency
82% AC-AC
86% DC-AC
85% AC-AC
87% DC-AC
88% AC-AC
89% DC-AC
89% AC-AC
88% DC-AC
Dimensions Dimensions (L x D x H)
20″ x 36.3″ x 59.7″
35.4″ x 37.6″ x 59.8″
Weight (lb)
900
910
915
2548
Altitude
6600 ft (2000 m)(Maximum without Derating)
Audible Noise
< 60 dBA at 1 m
< 65 dBA at 1 m
Features
Internal Make-Before-Break Maintenance Bypass Switch,
RS232 and Dry Contact Interface
Standards
UL 1778, cUL, NEC, ISO9001, ISO14001, ANSI C62.41 (IEEE
587), NEMA PE1-1993
Warranty
(See Toshiba Warranty Policy for Full Details.)
Service
7 x 24 Technical Support 1-877-867-8773 (1-UPS-TOS-UPS3)
rev 6/2010

 

Industries & Applications

  • Hospitals, clinics, and other medical facilities
  • “Lights-out” or “dark factory” manufacturing
  • Critical network switching & processing equipment
  • Large-scale PLC controls
  • Medium-to-larger data centers
  • Financial Institutions
  • Industrial applications
  • Pharmacological manufacturing

Request a quote

 

We respect your privacy and will never share your email address with anyone without your explicit permission.

Widely used in hospitals, clinics, and other medical facilities as a UPS power conditioner with battery backup, the G8000 Series offers a high crest factor that’s ideal for MRI, PET, CT and other medical devices that have a high current inrush. The G8000 has a unity power factor output that provides 20 percent more energy than what’s typical of UPS systems from other manufacturers. It’s also 100 percent generator compatible, and its low input-current harmonics eliminate the need for an oversized generator.

Features & Benefits

  • Ideal for hospitals, clinics, and other medical applications where power protection is critical
  • High crest factor is ideal for MRI, PET, CT and other medical devices that have a high current inrush
  • Unity power factor output provides 20 percent more energy than UPS systems from other manufacturers
  • 100 percent generator compatible— low input-current harmonics eliminate the need for oversized generator

Request a quote

Technical Specs

G8000 Specifications
Model #
T80S3K08KK 6XS2H
T80S3K10KK 6XS2H
T80S3K15KK 6XSNH
T80S3K22KK 6XSNH
T80S3K30KK 6XSNH
Input
Rated Output Capacity
80 KVA/80 KW
100 KVA/ 100 KW
150 KVA/150 KW
225 KVA/ 225 KW
300 KVA / 300 KW
Voltage
480 VAC (+10% to -15%)
Frequency
60 Hz (+/-5%)
Configuration
3 Phase; 3 Wire + GND
Input KW
90 KW
110 KW
165 KW
247 KW
318 KW
( 102 KW Charging)
(122 KW Charging)
(181 KW Charging)
(270 KW Charging)
(319 KW Charging)
Power Factor
> 0.99 PF Lagging
Walk-In Function
EEPROM Upgrade
Maximum Input Current
108 A Normal
135 A Normal
200 A Normal
303 A Normal
396 A Normal
(125 A Charging)
(150 A Charging)
(222 A Charging)
(338 A Charging)
(401 A Charging)
Reflected THD
< 5% Maximum @ 100% Load
6% Maximum @ 25% Load
Bypass
Configuration
Three-Phase; Four-Wire + Ground
Voltage
480/277V (±10%)
Frequency
60 Hz (±5%)
Bypass Overload Capacity
1000% for One Cycle, 500% for Two Cycles
Battery Backup
Number of Cells
180
Type
Lead Acid (Contact Factory for Alternative Options)
DC Nominal
360 V
DC Minimum
288 V
Float Charge
405 V
Ripple Current (without batteries)
AC Ripple on DC Bus: < 0.2% of DC Voltage
Back-up Time
Application Specific
Max DC Charging Current
30 A
30 A
30 A
30 A
30 A
Max Discharge
305
375
566
840
1120
Battery Capacity Required for Full Load Output
88 KWB
108 KWB
163 KWB
245 KWB
323 KWB
Output
Voltage
480Y/277V
Configuration
Three-Phase; Four-Wire + Ground
Voltage Regulation
±1% for 0 to 100%Balanced and Unbalanced Loads
Voltage Adjustment Range
±5% (In Increments of 1V)
Voltage Unbalance
±3% for 100% Linear Loads ±5% for 100% Non-Linear Loads
Crest Factor
2
Transient Voltage Response
±2% Maximum with a 100% Step Loads (Without Utilizing Batteries)
±1.5% Maximum with Loss/Return AC Input
±2% Maximum When Load Transfers To/From Bypass
Transient recovery time
< 50 ms
Frequency
60 Hz
Frequency Synchronous Range
±0.5 Hz, ±1 Hz, + 1.5Hz (Selectable)
Frequency Slew Rate
1 Hz/Sec
Frequency Regulation
±0.01% in free running mode
Current
96 A
120 A
180 A
271 A
361 A
Power Factor
1.0 PF Lagging: 32 – 86 °F (0 – 30 °C) 0.8 PF Lagging: 86 – 104 °F (30 – 40 °C)
Overload Capacity
125% for 10 Minutes, 150% for 60 Seconds
Voltage THD
< 3% Max with 100% Linear Load/5% Max with 100% Non-Linear Load
Reliability
MTBF
200,000 Hours
Efficiency
@ 25% Load
83.9%
86.4%
89.6%
87.9%
88.8%
@ 50% Load
85.3%
90.1%
91.7%
91.0%
91.7%
@ 75% Load
90.0%
91.2%
92.3%
92.3%
92.7%
@ 100% Load
90.6%
91.0%
93.0%
91.9%
92.0%
Environment
Cooling
Forced Air
Paint Color
Sherwin Williams HHT2-7055, 079 Beige Texture
Weight
1390lb. (630 kg)
1740 lb. (789 kg)
2467 lb. (1119kg)
2980 lb. (1352 kg)
4575 lb. (2075 kg)
Weight (Shipping)
1440 lb. (653 kg)
1790 lb. (812 kg)
2556 lb. (1159 kg)
3069 lb. (1392 kg)
4725 lb. (2143 kg)
Floor Loading
171 Lbs/ft2 (1037 kg/m2)
214 Lbs/ft2 (1299 kg/m2)
203 Lbs/ft2 (991 kg/m2)
245 Lbs/ft2 (1196 kg/m2)
255 Lbs/ft2 (1245 kg/m2)
Dimension – Width
36.8 in. (935 mm)
55.1 in. (1400 mm)
76.8 in. (1951 mm)
Depth
32.5 in. (826 mm)
31.8 in. (808 mm)
35.7 in. (907 mm)
Height
79.2 in. (2012 mm)
79.4 in. (2017 mm)
Power Cable Access
Bottom Access
Top or Bottom Access
Top Access
Clearance Required
Top: 15.75″ (400 mm)
Front: 43 7/16″ (1100 mm)
Back/Left/Right Sides: Zero
Enclosure
NEMA 1
Heat Loss to be Removed @ Full Load
28,387 BTUs/Hour
34,222 BTUs/Hour
44,506 BTUs/Hour
68,240 BTUs/Hour
85,300 BTUs/Hour
Audible Noise
65 DBA @ 1m Typical
68 DBA @ 1 m Typical
72 DBA @ 1 m Typical
Operating Temperature
32? to 86?F (0? to 30?C) for 1.0 PF 32? to 104?F (0? to 40?C) for 0.8 PF
Operating Humidity
30% to 90% Non-Condensing
Operating Altitude
3200 Feet (1000 m)
Listings/Standards
UL 1778; UL 17025, cUL 22.2, No. 107.1; ANSI C62.41 (IEEE 587 Cat B) NFPA 70; OSHA; ISO 9001; IEC298 IP20
Monitoring
Warranty
Three Years Parts and Labor
Dry Contacts Included
Yes for Input and Output Signals
RS232 Port
Included
Intelligent Monitoring (Optional)
SNMP; Modbus RTU; Modbus TCP; BACNET, METASYS
Display
LCD Touch-Panel for Local Monitoring, Operation, and Control
EPO
Emergency Power Off
Included
Configuration
Input Conv.
6-Diode Bridge Rectifier
Battery Cct
IGBT Chopper
Out. Inv.
IGBT Converter with PWM

 

Industries & Applications

  • Hospitals, clinics, and other medical facilities
  • “Lights-out” or “dark factory” manufacturing
  • Large data centers or IT systems
  • Critical network switching & processing equipment
  • Large-scale PLC controls

Request a quote

 

We respect your privacy and will never share your email address with anyone without your explicit permission.

 

Boasting efficiencies that are 10-to20 percent beyond current industry standards, the G9000 Series is excellent for N+1 parallel systems where loads are typically 30-to 40 percent. Designed for either standalone or parallel use, the G9000 Series allows you to configure as many of eight units— without requiring the use of a special switchgear cabinet.

Toshiba proprietary technology and double-conversion topology provide AC/DC/AC efficiencies of up to 97 percent at loads from 50 to 100 percent. In fact, even at 20 percent loading, the efficiency remains greater than 94 percent. Available in capacities of 100, 160, 225, 300, 500, 750, and 1000kVA, the G9000 Series comes with an industry-leading three-year onsite warranty.


Features & Benefits

  • Efficiencies 10-to20 percent beyond current industry standards
  • Excellent for N+1 parallel systems where loads are typically 30-to 40 percent
  • Designed for either standalone or parallel use
  • Configure as many of eight units— without requiring the use of a special switchgear cabinet
  • Double-conversion topology provides AC/DC/AC efficiencies of up to 97 percent at loads from 50 to 100 percent.
  • Efficiency remains greater than 94 percent even at as low as 20-percent loading
  • Available in capacities of 100, 160, 225, 300, 500, 750, and 1000kVA
  • Comes with an industry-leading three-year onsite warranty

Request a quote

 

Technical Specs

G9000 Standard Specifications
MODEL NUMBER
T90S3S10KS6XSN
T90S3S16KS6XSN
T90S3S22KS6XSN
T90S3S30KS6XSN
T90S3S50KS6XSN
T90S3S75KS6XSN
T90S3S01MS6XSN
Capacity (KVA/KW)
100/90
160/144
225/202.5
300/300
500/500
750/750
1000/1000
Topology True On-Line, Double Conversion, Advanced Multi-Level IGBT Technology
INPUT
Voltage 480 V, Three-Phase, Three-Wire + Ground/Bypass Input; 480 V, Three-Phase, Three-Wire + Ground
Voltage Range 480 V, -20% to +15% (384 to 552 V Without Utilizing Battery)
Power Factor Greater than 0.99
Current THD < 3% at 100% Load (No Input Filter Required)
Frequency 60 Hz (±10%)
OUTPUT
Voltage 480 V, Three-Phase, Three-Wire + Ground
Frequency 60 Hz, ±0.01% (In Free-Running Mode)
Voltage Regulation ±1.0% (0.5% Typical)
Power Factor 0.9 Lagging 1.0 (Unity)
Voltage THD < 2% for Linear Load; < 5% for Non-Linear Load
Overload (Inverter) 125% for 2 Minutes; 150% for 60 Seconds 125% for 10 Minutes; 150% for 60 Seconds
Overload (Bypass) 1000% for One Cycle 500% for One Cycle
BATTERY
DC Link 480 VDC Nominal
ENVIRONMENT
Temperature Range 32° to 104°F (0° to 40°C)
Relative Humidity 5% to 95% Non-Condensing
Heat Rejection 13.5 kBTU/Hour 17.8 kBTU/Hour 25.1 kBTU/Hour 31.7 kBTU/Hour 52.8 kBTU/Hour 79.2 kBTU/Hour 112.8 kBTU/Hour
Efficiency (Full Load) 95.80% 96.50% 96.50% 97.00% 97.00% 97.00% 96.80%
Efficiency (20% Load) 92.50% 94.70% 94.90% 94.40% 94.80% 95.50% 95.50%
Altitude 7380 Feet Maximum Without Derating (2250 Meters) 6500 Ft. max
Audible Noise 70 DBA at 1 Meter 73 DBA at 1 Meter
DIMENSIONS
Dimensions (W x D x H) 27.6 x 32.8 x 80.6 in. 35.4 x 32.8 x 80.6 in. 51.2 x 32.7 x 80.7 in 70.9 x 32.7 x 80.7 in. 90.6 x 32.7 x 80.7 in. 118.2 x 35.5 x 80.7 in.
700 x 832 x 2047 mm 900 x 832 x 2047 mm 1300 x 832 x 2050 mm 1800 x 832 x 2050 mm 2300 x 832 x 2050 mm 3003 x 902 x 2050 mm
Weight 855 lbs. 1160 lbs. 1230 lbs. 2260 lbs. 3360 lbs. 4250 lbs. 6613 lbs.
388 kg 526 kg 558 kg 1025 kg 1525 kg 1928 kg 3000 kg
FEATURES
Digital Signal Processor (DSP) Control, Fully Digital IGBT Converter & Inverter, High Efficiency Over Wide Load Range,
Transformer-Less Design, N+1 & N+N (Up to Eight in Parallel) Capability, Dual-Input Feed, Electronic Battery Isolation,
RS232 and Dry Contact Interface, Small Footprint, & Lightweight Design
STANDARDS
UL 1778 and UL-C Listed, ISO9001, ISO14001, ANSI C62.41(IEEE 587), FCC Class A, Article 47, Part 15.B UL 1778 and UL-C Listed, ISO9001, ISO14001, ANSI C62.41(IEEE 587), IEC 62040-2 Cat.3
WARRANTY
Three Years Onsite (Optional Two-Year Extended Warranty); See Toshiba Warranty Policy for Full Details
SERVICE
24-Hour, 365-Day Technical Support 877-226-3311

 

Industries & Applications

  • Police & fire emergency call centers
  • Military applications
  • “Lights-out” or “dark factory” manufacturing
  • Large data centers or IT systems
  • Critical network switching & processing equipment
  • Large-scale PLC controls

Request a quote

 

We respect your privacy and will never share your email address with anyone without your explicit permission.