Noted for its versatility, and offering the largest input voltage/frequency window in the industry, the 4200FA Series is designed to be a high-performance state-of-the-art commercial or industrial UPS system suitable for use across a wide breadth of industrial UPS system applications.

Features include true online double-conversion, an input power factor better than 98 percent, and input current THD less than 3 percent. Frontend IGBT design allows the 4200FA to work optimally from zero to 100 percent load with less than 3 percent THD on the input, allowing for generator single-sizing. Proprietary technology lengthens battery life. The CT models feature internal batteries and maintenance bypass— without the need for additional cabinets. Comes with a standard three year warranty.


Features & Benefits

  • Largest input voltage/frequency window in the industry
  • Suitable for use across a wide breadth of industries and applications
  • True online double-conversion
  • Input power factor better than 98 percent
  • Input current THD less than 3 percent
  • Frontend IGBT design works optimally from zero to 100 percent load with less than 3 percent THD on the input—allowing for generator single-sizing
  • Proprietary technology lengthens battery life
  • Three year warranty

Request a quote

 

Technical Specs

4200FA CT Standard Specifications
Model Number
T42F3F150XAMBN
T42F3F250XAMBN
T42F3F300XAMBN
T42F3F500XAMBN
Capacity kVA/kW
15/12
25/20
30/24
50/40
Topology
True On-line, Double Conversion, IGBT Pwm, with Active
Input Power Factor Correction
Input Voltage
208/120 V, 3 Phase, 4 w + Gnd
Voltage Range
+10% to -30%; +20% to -30% online (without utilizing
battery)
Power Factor
Greater than 0.99
Current THD
Less than 3%
Frequency
50/60 Hz (Range 45 to 65 Hz)
Current Limit
115% Maximum
Output Voltage
208/120 V, 3-Phase, 4 w + Gnd
Frequency
50/60 Hz � 0.01% (Can be Used as a Frequency Converter)
Voltage Regulation
< 1% Balanced, 100% Load Step / < 2% Unbalanced,
100% Load Step
Overload (Inverter)
125% for 90 Seconds, 150% for 30 Seconds
Overload (Bypass)
125% for 10 Minutes, 1000% for 10 milliseconds
Battery Time (Full / Half Load)
9/26 Minutes
4/13 Minutes
3/10 Minutes
4.5/14 Minutes
DC Link
288 VDC
Ripple Voltage
< 0.5% DC
Environment Temperature Range
0 to 40� C (Operating) / -20 to +50� C (Storage)
Relative Humidity
0 to 95% Non-Condensing
Heat Rejection
8,988 BTUs
12,043 BTUs
14,451 BTUs
18,611 BTUs
Efficiency
82% AC-AC
86% DC-AC
85% AC-AC
87% DC-AC
88% AC-AC
89% DC-AC
89% AC-AC
88% DC-AC
Dimensions Dimensions (L x D x H)
20″ x 36.3″ x 59.7″
35.4″ x 37.6″ x 59.8″
Weight (lb)
900
910
915
2548
Altitude
6600 ft (2000 m)(Maximum without Derating)
Audible Noise
< 60 dBA at 1 m
< 65 dBA at 1 m
Features
Internal Make-Before-Break Maintenance Bypass Switch,
RS232 and Dry Contact Interface
Standards
UL 1778, cUL, NEC, ISO9001, ISO14001, ANSI C62.41 (IEEE
587), NEMA PE1-1993
Warranty
(See Toshiba Warranty Policy for Full Details.)
Service
7 x 24 Technical Support 1-877-867-8773 (1-UPS-TOS-UPS3)
rev 6/2010

 

Industries & Applications

  • Hospitals, clinics, and other medical facilities
  • “Lights-out” or “dark factory” manufacturing
  • Critical network switching & processing equipment
  • Large-scale PLC controls
  • Medium-to-larger data centers
  • Financial Institutions
  • Industrial applications
  • Pharmacological manufacturing

Request a quote

 

Request a Quote

Request a Quote from N1 Critical Technologies
  • Thank you for your interest on N1 Critical Technologies Inc. To contact us via email, please complete the form below and our representative will contact you. Our mailing address is 2949 Venture Drive, Suite 108 Janesville, WI 53546. Our telephone number is (855)-665-3829.

We respect your privacy and will never share your email address with anyone without your explicit permission.

0 replies

Leave a Reply

Want to join the discussion?
Feel free to contribute!

Leave a Reply

Your email address will not be published. Required fields are marked *