TOSHIBA 4200FA Series
Noted for its versatility, and offering the largest input voltage/frequency window in the industry, the 4200FA Series is designed to be a high-performance state-of-the-art commercial or industrial UPS system suitable for use across a wide breadth of industrial UPS system applications.
Features include true online double-conversion, an input power factor better than 98 percent, and input current THD less than 3 percent. Frontend IGBT design allows the 4200FA to work optimally from zero to 100 percent load with less than 3 percent THD on the input, allowing for generator single-sizing. Proprietary technology lengthens battery life. The CT models feature internal batteries and maintenance bypass— without the need for additional cabinets. Comes with a standard three year warranty.
Features & Benefits
- Largest input voltage/frequency window in the industry
- Suitable for use across a wide breadth of industries and applications
- True online double-conversion
- Input power factor better than 98 percent
- Input current THD less than 3 percent
- Frontend IGBT design works optimally from zero to 100 percent load with less than 3 percent THD on the input—allowing for generator single-sizing
- Proprietary technology lengthens battery life
- Three year warranty
Technical Specs
4200FA CT Standard Specifications
|
|||||
Model Number
|
T42F3F150XAMBN
|
T42F3F250XAMBN
|
T42F3F300XAMBN
|
T42F3F500XAMBN
|
|
Capacity | kVA/kW |
15/12
|
25/20
|
30/24
|
50/40
|
Topology |
True On-line, Double Conversion, IGBT Pwm, with Active
Input Power Factor Correction |
||||
Input | Voltage |
208/120 V, 3 Phase, 4 w + Gnd
|
|||
Voltage Range |
+10% to -30%; +20% to -30% online (without utilizing
battery) |
||||
Power Factor |
Greater than 0.99
|
||||
Current THD |
Less than 3%
|
||||
Frequency |
50/60 Hz (Range 45 to 65 Hz)
|
||||
Current Limit |
115% Maximum
|
||||
Output | Voltage |
208/120 V, 3-Phase, 4 w + Gnd
|
|||
Frequency |
50/60 Hz � 0.01% (Can be Used as a Frequency Converter)
|
||||
Voltage Regulation |
< 1% Balanced, 100% Load Step / < 2% Unbalanced,
100% Load Step |
||||
Overload (Inverter) |
125% for 90 Seconds, 150% for 30 Seconds
|
||||
Overload (Bypass) |
125% for 10 Minutes, 1000% for 10 milliseconds
|
||||
Battery | Time (Full / Half Load) |
9/26 Minutes
|
4/13 Minutes
|
3/10 Minutes
|
4.5/14 Minutes
|
DC Link |
288 VDC
|
||||
Ripple Voltage |
< 0.5% DC
|
||||
Environment | Temperature Range |
0 to 40� C (Operating) / -20 to +50� C (Storage)
|
|||
Relative Humidity |
0 to 95% Non-Condensing
|
||||
Heat Rejection |
8,988 BTUs
|
12,043 BTUs
|
14,451 BTUs
|
18,611 BTUs
|
|
Efficiency |
82% AC-AC
86% DC-AC |
85% AC-AC
87% DC-AC |
88% AC-AC
89% DC-AC |
89% AC-AC
88% DC-AC |
|
Dimensions | Dimensions (L x D x H) |
20″ x 36.3″ x 59.7″
|
35.4″ x 37.6″ x 59.8″
|
||
Weight (lb) |
900
|
910
|
915
|
2548
|
|
Altitude |
6600 ft (2000 m)(Maximum without Derating)
|
||||
Audible Noise |
< 60 dBA at 1 m
|
< 65 dBA at 1 m
|
|||
Features |
Internal Make-Before-Break Maintenance Bypass Switch,
RS232 and Dry Contact Interface |
||||
Standards |
UL 1778, cUL, NEC, ISO9001, ISO14001, ANSI C62.41 (IEEE
587), NEMA PE1-1993 |
||||
Warranty |
(See Toshiba Warranty Policy for Full Details.)
|
||||
Service |
7 x 24 Technical Support 1-877-867-8773 (1-UPS-TOS-UPS3)
|
||||
rev 6/2010 |
Industries & Applications
- Hospitals, clinics, and other medical facilities
- “Lights-out” or “dark factory” manufacturing
- Critical network switching & processing equipment
- Large-scale PLC controls
- Medium-to-larger data centers
- Financial Institutions
- Industrial applications
- Pharmacological manufacturing